  rev. aa, 19 - may - 201 1 preliminary page 1 / 13 www.power - one.com abc400 - 10xxg data sheet ap plications ? features ? ? ? ? ? ? ? 3 ? ? description this is a compa ct and efficient series of ac - dc power supplies suited for telecom, datacom and many other applications. t his family meets the international information technology safety standards with the ce - mark for the european low voltage directive (lvd). t heir high efficiency allows a very minimal power loss in end equipment, resulting in higher reliabil ity, ease of thermal management and regulatory approvals for an environmentally friendly end product. content 1 ordering information ................................ ............. 2 2 overview ................................ ................................ ....... 2 3 absolute maximum ratings ................................ ... 3 4 environmental and mechanical ......................... 3 5 input specifications ................................ ................ 3 5.1 input fuse ................................ ............................ 4 5.2 inrush current ................................ ................. 4 5.3 input under - voltage ................................ ....... 4 5.4 power factor correction ........................... 4 5.5 efficiency ................................ ............................ 4 6 output specifications ................................ ............ 5 7 protection ................................ ................................ ... 8 7.1 overvoltage protection .............................. 8 7.2 current limitation ................................ ........... 8 8 power good signal ................................ .................. 9 9 electromagnetic compatibility ......................... 9 9.1 immunity ................................ ................................ 9 9.2 emission ................................ .............................. 10 10 safety / approvals ................................ ............... 10 11 mechanical ................................ .............................. 10 11.1 dimensions ................................ ....................... 11 11.2 connections ................................ ................... 13 www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 2 / 13 www.power - one.com abc400 - 10xxg data sheet 1 ordering information product family o utput power dash # output s standard: 0 s - type: 1 - 9 vo - voltage rohs compliant abc 400 - 10xx 40 0 w - 1 0 12vdc / 24 vdc / 48vdc g 2 overview the abc400 - 10 xx g is a high efficiency and high power density ac to dc power supply . it incorporates interleaved transition mode pfc converter and well proven two - fet forward converter, providing increased system reliability and high efficie ncy. w ith around 1 m/s system air cooling, abc400 - 10 12 g can delivery up to 360 w continuous output power and 40 8 w for abc400 - 10 24 g and abc400 - 10 48 g figure 1 : abc400 - 10 xx g b lock d iagram vo www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 3 / 13 www.power - one.com abc400 - 10xxg data sheet 3 absolute maximum ratings stresses in excess of the absolute maximum ratings may cause performance degradation, adversely affect long - term reliability, and cause p ermanent damage to the supply . parameter conditions / description min nom max unit v i maxc max continuous input continuous transient, 60 ms 264 300 vac vac 4 environmental and mechanic al parameter conditions / description min nom max unit t a ambient temperature v i min to v i max , i o nom , i sb nom - 1 0 +5 0 c t aext extended temp range de rat ed outpu t + 5 0 + 70 c t s storage temperature non - op erational - 4 0 + 85 c dimensions width 76.2 mm height 38.1 mm depth 127.0 mm m weight 0.5 kg 5 input specifications general condition: t a = - 1 0 5 0 c unless otherwise noted. active fan air cooling required : 200 lfm (1 m/s) parameter cond itions / description min nom max unit v i nom nominal input voltage 100 2 4 0 vac v i input voltage ranges normal operating ( v i min to v i max ) 90 264 vac i i max max input current 6 .5 a rms i i p inrush c urrent l imitation v i nom =115 vac , t = 25c (see figure 2 ) v i nom =230 vac , t = 25c (see figure 3 ) 30 60 a p f i input frequency 47 50/60 63 hz pf power f actor v i nom = =264vac, > 0. 5 i o nom 0.9 w/va v i on turn - on input vo ltage 1) ramping up 8 0 88 vac v i off turn - off input voltage 1) ramping down 7 2 8 0 vac v i nom =230vac, 0. 5 ? i o nom , v o nom , t a = 25 c 89 % v i nom =230vac, 1.0 ? i o nom , v o nom , t a = 25 c 90 t hold hold - up time after last ac zero point, v o within regulation, v i = 115 vac, p o nom 1 6 ms 1) the power supply is provided wit h a minimum hysteresis of 8 v during turn - on and turn - off within the ranges. www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 4 / 13 www.power - one.com abc400 - 10xxg data sheet 5.1 input fuse a slow - blow 8 a i nput fuse s ( 5 20 mm) in series with l ive line inside the power supply protect s against severe defects . t he fuse and a vdr form together with the inp ut filter an effective protection against high input transients. 5.2 inrush current the ac - dc power supply exhibit s an x - capacitance of only 1 .47 f, resulting in a low and short peak current, when the supply is connected to the mains. t he internal bulk capacitor will be charged through an power resistor which will limit the inrush current (see figure 2 and 3 ) . figure 2 : inrush current, v in = 1 15 vac, 9 0 ch 2 : v in ( 250 v/div), ch3 : i in ( 10 a/div) figure 3 : inrush current, v in = 230vac, 9 0 ch2 : v in (2 5 0v/div), ch3 : i in ( 1 0 a/div) 5.3 input under - voltage if the sinusoidal input voltage stays below the input under voltage lockout threshold v i on , th e supply will be inhibited. once the input voltage returns within the normal operating range, the supply will return to normal operation again. 5.4 power factor correction p ower factor correction (pfc) is achieved by controlling the input current waveform sync hronously with the input voltage. a specified pfc contr oller is implemented in the interleaved transition mode topology giving outstanding pfc results over a wide input voltage and load ranges. the input current will follow the shape of the input voltage. 5.5 efficiency t he high efficiency ( see figure 4, 5 and 6 ) is achieved by using state - of - the - art silicon power devices in conjunction with interleaved transition mode pfc topolog y minimizing www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 5 / 13 www.power - one.com abc400 - 10xxg data sheet switching losses. synchronous rectifiers on the output reduce the lo sses in the high current output path for abc400 - 1012g . s chottky diode and ultra fast diode are used as rectifiers for abc400 - 1024g and abc400 - 1048g due to the high output v oltage level. figur e 4 : efficiency vs. output power at 230vac, abc 4 00 - 1012g figure 5 : efficiency vs. output power at 230vac, abc 4 00 - 1024g figure 6 : efficiency vs. output power at 230vac, abc 4 00 - 1048g 6 output specifications g eneral c ondition: t a = - 1 0 +5 0 c unless otherwise noted. active fan air cooling required: 200 lfm (1 m/s) parameter conditions / description min nom max unit main output v o v o nominal output voltage 0.5 ? o , t amb = 25 c abc400 - 1012g 12.0 vdc abc400 - 10 24g 2 4 .0 vdc abc400 - 1048g 48 .0 vdc 76.0 78.0 80.0 82.0 84.0 86.0 88.0 90.0 92.0 0 100 200 300 400 po (w) efficiency (%) series1 76.0 78.0 80.0 82.0 84.0 86.0 88.0 90.0 92.0 0 100 200 300 400 po (w) efficiency (%) series1 76.0 78.0 80.0 82.0 84.0 86.0 88.0 90.0 92.0 0 100 200 300 400 po (w) efficiency (%) series1 www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 6 / 13 www.power - one.com abc400 - 10xxg data sheet v o set output set point accuracy 0.5 ? i o , t amb = 25 c abc400 - 1012g - 50 50 mv abc400 - 1024g - 75 75 mv abc400 - 1048g - 150 150 mv p o nom nominal output power abc400 - 1012g 0 276 360 w abc400 - 1024g 0 312 408 w abc400 - 1048g 0 312 408 w i o nom nominal output current abc400 - 1012g 0 23 30 a abc400 - 1024g 0 1 3 17 a abc400 - 1048g 0 6.5 8.5 a v o p - p output ripple voltage v o nom , i o nom , 20 mhz bw abc400 - 1012g 60 120 mvpp abc400 - 1024g 8 0 24 0 mvpp abc400 - 1048g 150 480 mvpp d v o load load regulation v i = v i nom , 0 - 100 % i o nom abc400 - 1012g - 360 50 360 mv abc400 - 1024g - 720 80 720 mv abc400 - 1048g - 1440 130 1440 mv d v o line line regulation v i =v i min i max abc400 - 1012g - 360 80 360 mv abc400 - 1024g - 720 120 720 mv abc400 - 1048g - 1440 150 1440 mv d v dyn dynamic load regulation o = 50% i o nom , i o = 5 0 o nom , d i o /dt = 1 a/s, o nom abc400 - 1012g - 0.6 0.25 0.6 v abc400 - 1024g - 1 .2 0.45 1.2 v abc400 - 1048g - 2.4 0.7 2.4 v t rec recovery time 2 ms t delay turn - on delay time required for output within regulation after intial application of ac input @90 vac 0 1 2 sec t rise turn on rise time v o = 1090% v o nom abc400 - 1012g 20 ms abc400 - 1024g 20 ms abc400 - 1048g 30 ms c load capacitive loading abc400 - 1012g 6600 f f f www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 7 / 13 www.power - one.com abc400 - 10xxg data sheet figure 7 : turn - on ac line 115 vac, full load ( 2 00 ms/div) ch1 : v o ( 10 v/div) ch 2 : vin ( 10 0 v/div) figure 8 : turn - on ac line 230 vac, full load ( 2 00 ms/div) ch1 : v o ( 10 v/div) ch 2 : vin ( 1 0 0 v/div) figure 9 : turn - off ac line 115 vac, full load ( 1 0 ms/div) ch1 : v o ( 10 v/div) ch 2 : vin ( 1 0 0 v/div) figure 10 : ac drop out 1 6 ms (10 0 ms/div) ch1 : v o ( 10 v/div) ch 2 : v in ( 100 v/div) figure 11 : ac drop out 30 ms ( 5 0 0 ms/div) , v o restart ch 1 : v o ( 10 v/div) ch 2 : v in (2 00 v/div) figure 1 2 : v o rise time at 115vac ( 2 0 ms/div) ch1 : v o ( 10 v/div) www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 8 / 13 www.power - one.com abc400 - 10xxg data sheet figure 1 3 : load transient v o ( 500 s/div), 8.5a < - > 17 a 2a/ s ch1 : v o ( 200m v/div) ch 2 : i o ( 5.0 a/div) figure 1 4 : load transient v o ( 1.0m s/div), 8.5a < - > 17 a , 2a/ s ch1 : v o ( 200 mv/div) ch 2 : i o ( 5 a/div) 7 protection parameter conditions / description min nom max unit f input fuses (l only ) not user accessible, time lag characteristic 8.0 a vo ov ov threshold abc400 - 1012g 14 .0 16 .0 vdc abc400 - 1024g 28.0 32.0 vdc abc400 - 1048g 53 57 vdc i o lim current limit v i > 90 vac, - 10 c < t a < 5 0 c abc400 - 1012g 31 . 5 3 3 .0 39 .0 a abc400 - 1024g 20.0 21.0 23.0 a abc400 - 1048g 8 . 9 10 11.1 a t sd over temperature on heat sinks automatic shut - down 1 00 c 7.1 overvoltage protection the ac - dc power supply provides a fixed threshold overvoltage (ov) protection implemente d with a hw comparator. once an ov condition has been triggered, the supply will shut down and latch the fault condition. t he latch can be unlocked by disconnecting the supply from the ac mains only . 7.2 current limitation the main output current limitation will decrease with linear derating to 50% at 70 oc if the ambient (inlet) temperature increases beyond 5 0 c (see figure 1 5 ) . www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 9 / 13 www.power - one.com abc400 - 10xxg data sheet figure 15 : output current limitation curve 8 power good s ignal the out - ok output gives a status indication of the converter and the output voltages. it can be used for control functions such as data protection, central system monitoring or as a part of a self - testing system. connecting the out - ok as shown in f igure 1 6 , vok <1.0 v indicates th at the output voltage(s) of the converter are within the range. note: u sing the potentiometer, the monitor level tracks the programmed output voltage. in an error condition, if the output voltage is out of range due to overload or an external overvoltag e, vok will approach vp. the output is formed by an npn transistor. the signal is isolated from the output. figure 1 6 : power good s ignal 9 electromagnetic compatibility 9.1 immunity note: most of the immunity requirements are derived from en 55024:199 8/a2:2003 . test standard / description criteria esd contact discharge en 61000 - 4 - 2, level 2 a rf susceptibility en 61000 - 4 - 3, level 3 a fast transient/ burst en 61000 - 4 - 4, l evel 3 b surge en 61000 - 4 - 5 , class 3 b rf conducted immunity en 61000 - 4 - 6, clas s 3 a voltage dips and interruptions en 61000 - 4 - 11 c 0 20 40 60 80 100 120 -10 0 10 20 30 40 50 60 70 ambient temperature(c) io (%) series1 www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 10 / 13 www.power - one.com abc400 - 10xxg data sheet magnetic fields en 61000 - 4 - 8 a 9.2 emission test standard / description criteria conducted emission en55022 / cispr 22: 0.15 30 mhz, qp and avg, s ingle unit class a 6 db m argin radiated emission en 5502 2 / cispr 22: 30 mhz 1 ghz, qp, single unit class a 6 db m argin harmonic e missions iec61000 - 3 - 2, vin = 100 vac/ 60 hz, 100% load class a iec61000 - 3 - 2, vin = 240 vac/ 50 hz, 100% load class a voltage fluctuation and flicker en61000 - 3 - 3 pass canad ian communications radio interference ices - 003 na rules for u nintentional r adiations fcc part 15, sub part - b na taiwan emi regulations bsmi: cns 13438 (95) na 10 safety / approvals maximum electric strength testing is performed in the factory according t o iec/e n 60950, and ul 60950. i nput - to - output electric strength tests should not be repeated in the field. power - one will not honor any warranty claims resulting from electric strength field tests. parameter description / conditions min nom max unit age ncy approvals ul 60950 - 1 second edition csa - c22.2 no. 60950 - 1 - 0 3 second edition iec 60950 - 1:2005 en 60950 - 1:2006 ce mark for lvd cb approval approved by independent body (see ce declaration) insulation safety rating input / c ase basic input / outpu t reinforced output / c ase functional d c creepage / clearance primary (l/n) to protective earth (pe) according to safety standard mm primary to secondary mm electrical strength test input to case 2 121 v d c input to output 42 42 v d c output and signals to case 500 v d c 11 mechanical www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 11 / 13 www.power - one.com abc400 - 10xxg data sheet 11.1 dimensions figure 1 7 : side view 1 figure 1 8 : top view figure 19 : side view 2 note: a 3d step file of the power supply casing is available on request. air flow direction air flow direction 19.05 2x 115 m3x0.5p thread hole f or customer syste m m ounting; mounting screw insert into psu chassis 5 .0 m m max. (2 holes o n each sid e) j1 j1-1 j2 j3 j1-5 j3-1 ou tsi d e ro w 1 2 7 0. 5 sn lab el i /o label 115 19.05 2x www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 12 / 13 www.power - one.com abc400 - 10xxg data sheet figure 2 0 : bottom view 2 figure 2 1 : front view m 3x0. 5 p t hr e a d h o l e f or c ust o m er syst e m m o u ti n g (4 p l ac es o n b o tt o m si d e) a a sect ion a-a 1 1 8 . 7 5 cus t o m er si d e m o u n ti n g scer w i ns ert i n t o p s u c h assis 5 . 0 m m m ax. 6 2 . 8 7 3 8. 1 0. 5 7 6. 2 0. 5 www.datasheet.co.kr datasheet pdf - http://www..net/
rev. aa, 19 - may - 201 1 preliminary page 13 / 13 www.power - one.com abc400 - 10xxg data sheet 11.2 connections pin name description input connector j1 j1 - 1 earth ac input earth j1 - 2 not fitted na j1 - 3 live ac input live j1 - 4 not fitted na j1 - 5 neutral ac input neutral output connector j2 j2 - outside row +vo +12v / +24v / +48v output j2 - inside row - vo +12v / +24v / +48v output return signal connector j3 j3 - 1 - vo sense output negative sense j3 - 2 +vo sense output positive sense j3 - 3 power good power good signal j3 - 4 power good return power good signal return mating parts ( cvilux or equivalent ) connector housing crimp terminal wire gauge j1 ci5105s0000 ci51t031be0 a wg#18 j 2 cp - 011 10030 ( for abc400 - 1012g) cp - 01100106 - hc awg#16 j3 ci3103s0000 ci31t021be0 awg#22 - 28 copyright ? 2010 power - one inc. all rights reserved. words and logos that are identified as trademarks and/or service marks are, unless noted otherw ise, the trademarks and service marks of power - one inc. in the u.s. and other countries. all other product or service names are the property of their respective holders. po wer - one products are protected under numerous u.s. and foreign patents and pending applications, maskwo rk rights, and copyrights. power - one reserves the right to make changes to any products and services at any time without notice. power - one assumes no responsibility or liability arising out of the application or use of any information, product, or service described herein except as expressly agreed to in writing by power - one inc. 1. nuclear and medical applications - power - one products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment use d in hazardous environments, or nuclear control systems without the express written consent of the respective divisional pres ident of power - one, inc. 2. technical revisions - the appearance of products, including safety agency certifications pictured on la bels, may change depending on the date manufactured. specifications are subject to change without notice. www.datasheet.co.kr datasheet pdf - http://www..net/


▲Up To Search▲   

 
Price & Availability of ABC400-1012G

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X